BECKHOFF KL6904 User Manual

Page 40

Advertising
background image

Operation

38

KL6904

The project is then displayed in text mode, and the user has to confirm consistency between the
information displayed and the currently projected application by re-entering the password.

The project is then started on the KL6904.

4.2.10.1 KL6904 project design limits

TwinSAFE connections

max. 7 or 15 (see Inserting a KL6904)

TwinSAFE blocks

48 max.

TwinSAFE groups

8 max.

Standard PLC inputs

max. 24 bit

Standard PLC outputs

max. 24 bit

Note

TwinSAFE connection

Only one TwinSAFE connection between two TwinSAFE terminals is possible.