KL6904

4.3.1.2

Diag 2 (red)

The Diag 2 LED indicates the state of the digital outputs.

Flashing Code

Meaning

rapid flickering, alternating with 1 flash pulse

Output 1: Open load or
current below minimum value of 20 mA or
current above maximum value of 500 mA

rapid flickering, alternating with 2 flash pulses

Output 2: Open load or
current below minimum value of 20 mA or
current above maximum value of 500 mA

rapid flickering, alternating with 3 flash pulses

Output 3: Open load or
current below minimum value of 20 mA or
current above maximum value of 500 mA

rapid flickering, alternating with 4 flash pulses

Output 4: Open load or
current below minimum value of 20 mA or
current above maximum value of 500 mA

rapid flickering, alternating with 5 flash pulses

Field potential too low

rapid flickering, alternating with 6 flash pulses

Field potential too high

rapid flickering, alternating with 7 flash pulses

Terminal temperature too low

rapid flickering, alternating with 8 flash pulses

Terminal temperature too high

rapid flickering, alternating with 9 flash pulses

Temperature difference error

rapid flickering, alternating with 10 flash pulses

error in output circuit through Open Load,
external supply or cross-circuit

These errors can only be reset by switching the power supply for the TwinSAFE terminal off and back on