Solar sizing worksheet – Codan Radio Radio Repeater Systems Training Guide User Manual
Page 35

RADIO REPEATER SYSTEM | TRAINING GUIDE
Chapter 3: Repeater System Equipment Page 27
SOLAR SIZING WORKSHEET
SITE NAME BRIDGE ARS
DATA POINT
LYTTON
AVERAGE YEARLY BRIGHT SUNSHINE HOURS (BSH)
1927
ADJUSTED (+ or - a +5 percent) TOTAL BSH
2023
AVERAGE PEAK HOURS PER DAY (total BSH x 0.0017) = B =
3.44
AVERAGE ANNUAL TEMPERATURE (at monitor point) c =
+9
ADJUSTED FOR SITE (c - adiabatic lapse rate) +20 = C =
23.5
DUTY CYCLE (shown as a decimal, eg. 8% = .08) = dc =
0.08
TOTAL DAILY NORMAL OPERATING HOURS a =
9
h
TOTAL STANDBY CURRENT (24 x Rx(I)) = b =
2.0
Ah
TOTAL TX CURRENT (a x Tx(I) x dc) = c =
1.6
Ah
TOTAL DAILY REQUIREMENT (b + c) = r =
3.6
Ah
REPEATER OPERATING VOLTAGE V =
12.5 Volts
BATTERY TYPE Ni-Cad VOLTS PER CELL v =
1.2
Volts
NUMBER OF CELLS REQUIRED IN SERIES (V/v) = VI =
10
cells
ONE BANK OF CELLS WILL GIVE (100 / r)
28 DAYS OF STORAGE
CHARGE VOLTAGE PER CELL CV =
1.4
Volts
REVERSE CURRENT DIODE OR REGULATOR LOSS D =
0
Volts
NOMINAL PANEL VOLTAGE (from manufacturers data) = m =
14
Volts
PANEL O/P VOLT REQ’D (D+R+(VIxCV)+(0.004(C x m))) = L =
15.8 Volts
PANEL CURRENT (from man. power graph) at L volts = M =
1.9
A
MODULE CURRENT PER DAY (B x M) = M1 =
6.5
A
NUMBER OF PANELS REQUIRED = (r / M1) =
0.5
modules