/switching higher current, Power, Power supply 1930085 – Dataprobe iPIO-2 Operation Manual User Manual

Page 6: Ipio-2, Specifications – elk-912-2, Switching higher current

Advertising
background image

iPIO-2816_v140120e

iPIO-2, iPIO-8, iPIO-16 Users Guide

Page 6

4.4.

Switching Higher Current


The ELK-912-2 (Item # 1340076) is a two relay board to
provide higher current switching for several of Dataprobe’s
remote control products. Each ELK-912-2 is two independent
relays, each with screw terminal connections. The relay
boards can be separated in to individual relays as required for
mounting.

To use the ELK-912-2 with the iPIO, connect the relay board to
the Output connections of the iPIO as shown below.

4.5.

Power


The iPIO-2, iPIO-8 and iPIO-16 are provided with a power supply, item 1930085. The supply is rated for 100-
240VAC 50/60 Hz. and is supplied with a line cord for North America. For locations outside of North America,
use an appropriate power adaptor or replace the cord with a suitable cord for your location. Power Supply
connection for the linecord is standard IEC C7.

Connect the power supply to the +5VDC connection on the iPIO. An LED next to the connector indicates
power on. The iPIO requires an approximately 1 minute boot-up process.

Power Supply 1930085

Input

100-240 VAC 50-60Hz

Output

5 VDC 4A

Linecord

NEMA 1-15P to IEC C7 2 meters

iPIO-2

The iPIO-2 can also be powered with Power over Ethernet (PoE) instead of the power supply.

PoE Specifications
4 Watts Maximum @ 48VDC

ELK-912-2 to iPIO

Connection

Specifications

– ELK-912-2

Operating Voltage : 12 VDC Nominal
Current Draw: 30 mA
Minimum Pull-in Voltage: 9VDC
Diode Protection Across Relay

Contact Rating:

7 Amps @ 30 VDC

10 Amps @ 125 VAC


Physical: 2.2” x 1.55” (56mm x 39mm)