4.5.3 SMB-0 through SMB-5 Double Torque Switch

NOTE: Torque settings must be made with the switch mounted in the actuator.

NOTE: See Section 4.3.3 for wiring connection requirements.

Piece numbers correspond to Figure 4.6 and Table 4.8.

To set the torque switch:
1. Verify all electric power is OFF.

2. For the open or close direction torque switch, loosen Machine Screw (piece #35) and set Pointer

(piece #7) at the desired torque setting. The higher the number, the higher the torque output of
the actuator.

3. Tighten Machine Screw (piece #35).

4. For torque seated valves, operate the valve electrically to seat the valve. Ensure tight shut-off by

tripping the torque switch contacts.

Figure 4.6 – SMB-0 through SMB-5 Double Torque Switch

3

4

3

2

1

2

5

1

3

41

27

18

9

6

36

27

27

39

29 16

42

47

3

20

21

22

10

15

28

45

37

33

17

4

2

1

31

43

44

7

39

35

5

25

12

13

30
34

25

25

23

8

11

01-473-0057-3