Flowserve 520si Digital Positioner User Manual

Page 10

Advertising
background image

10

approximately three seconds will initiate the calibration. If the
Config-Switches option is enabled, the settings of all the
configuration switches are read and the operation of the
positioner adjusted accordingly. The

Gain Selector switch is

also read and action will be taken to adjust the gain according
to the settings of the calibration switches as described in the
previous section. A

Quick-Cal can be aborted at any time by

briefly pressing the

Quick-Cal button and the previous settings

will be retained.

If the

Quick calibration switch (not to be confused with the

Quick-Cal button) is set to Auto and the valve/actuator as-
sembly has the necessary internal stops, the calibration will
complete automatically. While the calibration is in progress
you will notice a series of different lights flashing indicating
the calibration progress. When the lights return to a sequence
that starts with a green light, the calibration is complete. (See
the appendix for an explanation of the various light sequences.)

WARNING:

When operating using local control of the

valve, the valve will not respond to external
commands. Notify proper personnel that the valve
will not respond to remote command changes, and
make sure the valve is properly isolated.

If the

Quick calibration switch is set to Jog, the calibration

will initially close the valve then cause a small jump in the
valve position. The jog calibration process will only allow
the user to manually set the span; zero position is auto-
matically always set at the seat.
If an elevated zero is needed
a handheld or other PC based configuration software is re-
quired. The LEDs will then flash in a sequence of Y-R-R-G
(yellow-red-red-green) which indicates the user must now use
the

Jog keys to manually position the valve to the desired

100% position. Now press both

Jog buttons simultaneously

to proceed to the next step. The valve will then stroke and
then wait while flashing the Y-R-R-G sequence again, allow-
ing the user to adjust the valve position a second time to ex-
actly 100% using the

Jog buttons. When the stem is properly

positioned press both

Jog buttons simultaneously again to

register the 100% position and proceed. No more user ac-
tions are required while the calibration process is completed.
When the lights return to a sequence that starts with a green
light the calibration is complete. (See the appendix for an ex-
planation of the various light sequences.)

Local control of valve position — Can be done from the user
interface by holding both jog buttons and then simultaneously
pressing the

Quick-Cal button. While in this mode the LEDs

will flash a Y-G-R-R (yellow-green-red-red) sequence. To exit
the local control mode and return to normal operation, briefly
press the

Quick-Cal button.

Factory reset — hold

Quick-Cal button while applying power

and all of the internal variables including calibration will be
reset to factory defaults. The positioner must be re-calibrated
after a factory reset. Tag names and other user configured
limits, alarm settings, and valve information will also need to
be restored. A factory reset will always reset the command
source to analog 4-20 mA.

Special settings––several adjustments to the Logix 520 such
as split-range, MPC, soft stop, etc. cannot be set using the
local interface.

To set these parameters please refer to the appropriate com-
munications tool manual.

9.4 HART 275 HANDHELD COMMUNICATOR

The Logix 520 si supports and is supported by the HART 275
Handheld Communicator. The DD and the manuals listed be-
low can be obtained from the HART Communication Founda-
tion or from your Flowserve representative. For more infor-
mation please see the following guides:

Product Manual for the HART Communicator

• Logix 520 si Digital Positioner with HART 275

Communicator User Guide

9.5 USE OF SOFTTOOLS COMMUNICATION SOFTWARE

Flowserve corporation has written custom configuration and
diagnostic software for the Logix 500 si series called
SoftTools™. This software and the

SoftTools Quick Start Guide

are available from a Flowserve representative.

9.6 INTEGRATION OF THIRD-PARTY SOFTWARE

The Logix 520 si positioner can be used with:

– Siemens PDM™

– Fisher Rosemount AMS™

STOP!