Logix 520 si Symptoms and Solutions

Failure

Probable Cause

Corrective action

No LED is blinking

1. Current source below 3,6 mA

1.

Verify current source suppies at least 3,6 mA

2. Incorrect wiring polarity

2.

Check wiring for correct polarity

Erratic communications

1. Current source bandwidth not

1.

Maximum allowable current source rate of

limited to 25Hz

change is 924 mA per second

2. Maximum cable length or cable

2.

Check cable conductor size, length and

impedance exceeded

capacitance. Refer to ‘Cable Requirements’ on
page 11.

3. HART modem connected to PC RS-232 3.

Verify laptop battery is not low

port not receiving enough power

4. Interference with I.S. barrier

4.

Must use HART compatible I.S. barrier

5. Current source stripping (filtering)

5.

Use the HART filter (VHF) available from

HART signal

Flowserve (FLS part-No. 10156843)
Alternatively a 250 Ω and a 22 µF capacitor,
installed according to the following schematic
drawing can be used to establish communication

Unit does not respond

1. Unit is in digital command mode

1.

Switch to analog command mode with handheld

to analog commands

communicator or Soft Tools.

2. Error occurred during calibration

2. Correct calibration error. Recalibrate

Valve position reading

1. Stem position sensor mounting

1.

Reposition sensor

is not what is expected

is off 180 degrees

2. Stroke not calibrated

2.

Calibrate stroke

3. Tight shutoff MPC (Minimum

3.

No action

position cutoff) is active

4. Custom characterization or soft

4.

No action

stops active

Position is driven fully

1. Stroke not calibrated

1.

Calibrate valve stroke

open or closed and will

2. Inner-loop hall sensor not connected

2.

Verify hardware connections

not respond to command

3. Wrong air action entered in software

3.

Check ATO (Air-to-open) and ATC (Air-to-Close)
settings. Recalibrate

4. Actuator tubing backward

4.

Verify ATO/ATC actuator tubing

5. Electro-pneumatic converter

5.

Replace electro-pneumatic converter

malfunctioning

6. Control parameter inner-loop offset

6.

Adjust inner-loop and see if proper control

is too high/low

resumes

Sticking or hunting

1. Contamination of the

1.

Check air supply for proper filtering and meeting

operation of the positioner

electro-pneumatic converter.

ISA specifications ISA-7.0.01

2. Control tuning parameters not correct

2.

Lower proportional gain settings

Control system

250 Ω

22 µF

11 TROUBLE SHOOTING