Figure 19: driver module minimum pressure check – Flowserve Logix 1200e LGAIM0044 User Manual

Page 19

Advertising
background image

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

44-19

Checking or Setting the Driver Module Minimum
Pressure

Refer to Figure 19, proceed as follows:

1. Make sure valve is bypassed or in a safe condition.

2. Disconnect power from the positioner.

3. Remove the main cover and remove the

1

/

16

flexi-

ble tubing from the orifice.

4. Obtain a No. 10-32 x swivel elbow (Pneumadyne

part No. SFL-10 or equivalent) and a No. 10-32
extension (Clippard part No. 15010 or equivalent).

5. Remove the No. 10-32 x 0.016 orifice and gasket

(Figure 9) from the driver module using a

1

/

2-inch

nut driver. Take care to not misplace the gasket.

6. Screw in the 10-32 extension followed by the 10-32

x swivel elbow.

7. Direct the swivel elbow so the minimum pressure

test port is accessible.

8. Screw a No. 10-32 x

1

/

16

-inch barb fitting into the

test port, and screw the No. 10-32 x 0.016 orifice
into the end of the elbow as shown.

9. Connect the tubing from the internal regulator out-

put port to the orifice.

10.Using some

1

/

16

-inch flexible tubing, connect a 0 to

30 psi gauge to the minimum pressure set port.

11.Once the gauge is connected, reapply the posi-

tioner air supply. The minimum pressure should
now be registering on the gauge and must be 3.8 to
4.2 psi. If the minimum pressure is not correct, take
a

9

/

64

allen wrench and turn the minimum pressure

set screw located at the bottom of the driver mod-
ule (Figure 7) until the pressure is in the range indi-
cated. Cycle the positioner air supply several times
and recheck the minimum pressure and re-adjust, if
necessary, to ensure that the pressure has settled
within the range specified.

12.When the pressure is set, remove the air supply.

13.Remove the No. 10-32 x

1

/

16

barb and orifice from

the swivel elbow and then remove swivel elbow and
extension.

14.Replace the orifice and gasket as shown in

Figure 9 and reconnect the

1

/

16

inch flexible tubing

from the internal regulator output port to the orifice.
Reconnect the positioner air supply and power. The
positioner should now be ready to calibrate.

Figure 19: Driver Module Minimum

Pressure Check

Minimum Pressure
Test Port

No.10-32 x

1

/

16

B

a rb

No.10-32 x Swivel
TE

E (Pneumadyne

Part No. SFL-10)

No.10-32 x .016
Orifice

Pressure from Internal
Regulator to be tubed to
this orifice

No. 10-32 Extension
(Clippard Part No. 15010)

Advertising