Flowserve Logix 1200e LGAIM0044 User Manual

Page 42

Advertising
background image

44-42

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

Calibration

Red LED blinks after a Quick-Cal oper-
ation. Valve stays in fully open or
closed position.

1. Positioner configured for Linear

operation, but mounted on a
rotary actuator

1. Feedback linkage out of range

1. See Quick-Cal Function on

page 44-33.

1. See Stem Position Sensor on

page 44-12.

Yellow LED blinks after a Quick-Cal
operation

1. Valve did not fully stroke during

calibration (low or no air supply)

1. See Quick-Cal Function on

page 44-33. or 44-16.

Rotary valve has a dead band at the
fully open or closed position

1. Mechanical travel is not cen-

tered within the electrical mea-
surement range.

1. See Linear vs. Rotary on

page 44-32. or Stem Position
Sensor on page 44-12.

Red LED after loop current calibration

1. Applied Current is greater than

21 mA

1. Current source changed

between two values

1. See Command 100% Calibra-

tion Flag on page 44-33.

Control and Tuning

Valve will not saturate at closed posi-
tion

1. MPC may need to be enabled

1. See MPC (Minimum Position

Cutoff) on page 44-38.

Valve will not travel below or above a
certain limit

1. Soft limits not enabled

1. MPC not enabled

1. See Advanced Features on

page 44-40.

Sticking or hunting operation of the
positioner

1. Contamination of spool valve

assembly

1. Incorrect adjustment of P+I set-

ting

1. See Air Supply Requirements

on page 44-31. See Spool Valve
on page 44-35.

1. See Setting P+I Parameters on

page 44-34.

Large initial deviation. Only present on
initial power-up.

1. Inner loop offset not correct

1. See Setting P+I Parameters on

page 44-34.

Stem position movement is not linear
with command

1. Custom characterization not

enabled

1. See Custom Characterization

on page 44-40.

HART Communication

Will not communicate

1. Current source problem; May

need HART filter

1. Modem connection not operat-

ing correctly

1. HART module not enabled in

ValTalk software

1. See Current Source Interfer-

ence on page 44-35.

1. See HART Modem on

page 44-36.

1. In Options, select HART proto-

col

HART 275 communicator indicates
Generic after it connects to positioner

1. Handheld not programmed with

Valtek DD

1. Contact Flowserve Flow Con-

trol Division's Houston facility at
281.479.9500.

Table IV: Troubleshooting Logix 1200 Digital Positioner (2 of 3)

Failure or Problem

Probable Cause(s)

Refer to Section(s)