User Instructions Logix 505si - LGENIM0505-00 03/09

Colors

identifier

indication and resolution

YGRY

23

Analog output span too small - The span must be calibrated to a range greater than 3.0 mA. This error may be

cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last

good calibration.

R - - -

Any sequence starting with a red light indicates that there is an operational problem with the unit.

RRYY

25

Piezo voltage - (bad electronic assembly - replace.)

RYYR

26

Relay not operating – Most Likely the Air supply is disconnected. Could also be due to a bad pneumatic relay, failed

electronics, or a loose or bad connector from the electronics to the relay.

RYRY

27

Relay failed – Could be due to a bad pneumatic relay, failed electronics, or a loose or bad connector from the

electronics to the relay.

RGRR

28

Position Deviation – Indicates that he position has exceeded a fixed 20% error between command and position

for a period of time 5 times longer than the recorded stroke time. This error is usually seen when the positioner is

first mounted and powered up before a stroke calibration has been done. If the positioner is properly calibrated,

the air supply is correct, and the linkage is properly adjusted this error normally indicates that there is a mechanical

problem in the positioner, actuator, or valve that is preventing the valve from stroking properly. If a regulated air

supply connected to the actuator properly strokes the valve this indicates a bad positioner and should be replaced

if a calibration does not clear the error.

Logix 505si Status Condition Codes