Flowserve 505si Series Digital Positioner User Manual

Page 6

Advertising
background image

6

®

User Instructions Logix 505si - LGENIM0505-00 03/09

grounding Screw

The grounding screw, located inside the positioner

cover, should be used to provide the unit with an ad-

equate and reliable earth ground reference. This ground

should be tied to the same ground as the electrical con-

duit. Additionally, the electrical conduit should be earth

grounded at both ends of its run. The grounded screw

must not be used to terminate signal shield wires.

Compliance Voltage (Figure 3)

Output compliance voltage refers to the voltage limit

the current source can provide. A current loop system

consists of the current source, wiring resistance, barrier

resistance (if present), and the Logix 505si impedance.

The Logix 505si requires that the current loop system

allow for a 6,0 VDC drop across the positioner at maxi-

mum loop current.

CAUTiOn: Never connect a voltage source directly

across the positioner terminals. This could cause per-

manent circuit board damage.

flow capacity of the regulator must be larger than the

flow capacity of the positioner (7 Nm

3

/h @ 6 bar / 4,12

scfm @ 87 psi).

5. Connect the outlet connector Y of the positioner

to the actuator with tubing, independent of the action

(direct or reverse).

7

WiRing AnD gROUnDing gUiDELinES

Electrical connections: signal cable with cable passage

(NPT or M20 x 1,5) to terminals 2 x 2,5 mm

input signal: 4 – 20 mA

nOTE: Observe the minimum requirements of voltage

and equivalent electrical load: 6,0 VDC / 300

/ at

20 mA

The performance is ensured only for a minimum input

current of 3,6 mA.

For wiring, the following notes should be observed:

nOTE: The input loop current signal to the Logix 505si

should be in shielded cable. Shields must be tied to a

ground at only one end of the cable to provide a place

for environmental electrical noise to be removed from

the cable. In general, shield wire should be connected

at the source. (Figure 2)

Connect the 4-20 mA current source to terminals +11

and -12 (Figure 2).

Figure 2: Wiring Diagram

Table 10: Connection Table

Connection

Description

+11

Input+ 4..20 mA

-12

Input- 4..20 mA

Y (0

⇒)

Pneumatic output signal (outlet)

Z (0

⇐)

Air supply

Internal Housing

EARTH Terminal

4-20 mA Signal

Connect Shield at Source Ground

-

+

4-20 mA Current Source

Shielded Cable

Y

Z

Advertising