User Instructions Logix 505si - LGENIM0505-00 03/09

10 TROUbLESHOOTing LOgix 505Si DigiTAL POSiTiOnERS

Failure

Probable Cause

Corrective action

No LED is blinking

1. Current source below 3.6 mA

2. Incorrect wiring polarity

1. Verify current source is outputting at least 3,6 mA

2. Check wiring for correct polarity

Unit does not respond

to analog commands

1.Error occurred during calibration

1. Correct calibration error. Recalibrate

Valve position reading is

not what is expected

1. Stroke not calibrated

2. Stem position sensor mounting

is off 180 degrees

1. Recalibrate

2. Orient sensor properly

Position is driven fully

open or closed and will

not respond to command

1. Stroke not calibrated

1. Calibrate valve stroke

2. Inner-loop hall sensor not connected

2. Verify hardware connections

3. Wrong air action set on DIP switch

3. Check ATO (Air-to-open) and ATC
(Air-to-Close) settings. Recalibrate

4. Actuator tubing backward

4. Verify ATO/ATC actuator tubing

5. Electro-pneumatic converter

5. Replace electro-pneumatic converter

malfunctioning

Sticking or hunting

operation of the posi-

tioner

1. Contamination of the electro-

pneumatic converter.

1. Check air supply for proper filtering

and meeting ISA specifcations ISA-7.0.01

2. Control gain set too high

2. Switch to low gain setting