System malfunctions – Flowserve LRG 16-40 User Manual

Page 24

Advertising
background image

4

Causes

Faulty installation and/or configuration of CAN bus components, excessive temperatures in the devices,

defective electronic component parts or electromagnetic interferences of the supply system can result

in system malfunctions.
Other malfunctions are:

n

Incorrect communication in the CAN bus system

n

Overloading of the 4 V power supply unit that is integrated in the control unit

System Malfunctions

Note

Before carrying out the systematic malfunction analysis please check:
Wiring:

Is the wiring in accordance with the wiring diagrams?

Is the polarity of the bus lines always correct?

Are the bus lines of the first and last devices provided with 0 Ω terminating resistors?
Node ID:

Are all node ID settings correct?

Note that no node ID setting must be used twice!
Baud rate:

Does the baud rate setting correspond with the cable length?

Is the baud rate setting of all devices identical?