Annex, Control units sensors – Flowserve LRG 16-40 User Manual

Page 29

Advertising
background image

9

Annex

CAN bus

All devices (level, conductivity) are interconnected via CAN bus. The CANopen protocol is used for the

data exchange between the equipment groups. All devices have an electronic address – the node ID.

The four-core bus cable serves as power supply and data highway for high-speed data exchange.
The CAN address (node ID) can be set between

1 and 123.

The conductivity electrode LRG x-40 has already been configured at our works for operation with

other GESTRA components and can be used straight away without having to set the node ID.

Factory set node IDs

Individual node IDs must be set manually in the respective equipment.

Please observe the pertinent installation instructions.

Control Units

Sensors

NRS1-40

ID:001

NRS 1-41

ID:006

NRS 1-42

ID:020

NRS 2-40

ID:039

NRR 2-40

ID:040

LRR 1-40

ID:050

NRG 16-40 ID:002
NRG 16-40 ID:003
NRG 16-41 ID:007
NRG 16-42 ID:021
NRG 26-40 ID:041

LRG 16-40 ID:051

Node ID

Should it be necessary to establish other node IDs please take the interdependence of the equipment

into consideration and assign the node IDs for the individual group components according to the

following table:

Controller

URZ 40a

Intermittent

blowdown valve

BAE 3x-40

Control unit

LRR 1-40

Conductivity

electrode

LRG 1x-40

Reserved

X – 1

X

X + 1

X + 2

49

50

51

52

Factory setting

Reserved area

Advertising
This manual is related to the following products: