Technical data – Flowserve LRG 16-40 User Manual

Page 8

Advertising
background image

8

LRG 16-40, LRG 17-40

– continued –

Measuring cycle

 sec.
Accuracy

5 %, referred to conductivity readings without temperature compensation
Temperature compensation

Type of temp. compensation can be adjusted with URB or SPECTORcontrol:

n

Temperature compensation AUTO:

with conductivity/temperature curve characteristic of the installation.

n

Temperature compensation NORM:

with standard conductivity/temperature curve.

n

Temperature compensation LINEAR:

with set temperature coefficient (Tk).

Time constant T (measured as specified in DIN 3440)

Temperature: 9 sec.

Conductivity: 4 sec.
Input/Output

CAN bus interface with power supply 8 – 36 V DC, short circuit protected
Data exchange

CAN-bus to ISO 898, CANopen protocol
Power consumption

3.8 W
Fuse

Electronic thermal fuse Tmax 85°C, hysteresis -K.
Indicators and adjustors

Two LEDs for internal status messages.

One 0-pole code switch for node-ID and baud rate settings.
Electric connection

M  sensor connector, 5 poles, A coded

M  sensor jack, 5 poles, A coded
Protection

IP 65 to EN 6059
Ambient temperature

Max. 70°C
Weight

Approx. .5 kg

Technical Data

– continued –

Advertising
This manual is related to the following products: