Viewing trace Data

Selecting View Trace Data will result in the following display
presuming valid collection of data. The FDA Trace supports
data comparison to an existing saved file.

FDA Trace

Speed Trace

FDA and sPeeD Analysis explanation

The values for the X-axis are in RPM. The values for the Y-axis
are the relative magnitude of the power that the various rotating
components of the actuator are developing mechanically over
the speed ranges. If the magnitude at any given RPM changes
from the stored baseline FDA, then compare the x-axis RPM
for the suspect power magnitude against the expected working
RPM for the components in the actuator. Any component that
is expected to operate at the suspect RPM could be at risk
of excessive wear, and the actuator should be included in a
targeted preventive maintenance program. The suspect parts
could be ordered in advance of the preventive maintenance to
ensure that the downtime will be minimized.

Note: At the current time, the power magnitudes are relative
values.

Operation Log lists parameters associated with the MX/QX
operation since the last reset. This function is a real-time log.