Attaching the front cover – GAI-Tronics 12831-007, 12831-008 Hazardous Area ICS Termination PCBA Upgrade Kits User Manual

Page 6

Advertising
background image

Pub. 42003-268A

M

ODEL

12831-007

&

12831-008

H

AZARDOUS

A

REA

ICS

T

ERMINATION

PCBA

U

PGRADE

K

ITS

Page

6 of 6

f:\standard ioms - current release\42003 kit manuals\42003-268a.docx
02/14

Attaching the Front Cover

1. After all connections have been completed, inspect and clean the machined flange joint surface of

both the cover and the box. Surfaces must be smooth, free of nicks, scratches, dirt or any foreign
particle build-up that would prevent a proper seal. Surfaces must seat fully against each other to
provide a proper explosion-proof joint. Clean surfaces by wiping with a clean lint-free cloth.

2. Apply a light coat of Killark “LUBG” lubricant to flange surfaces and close the cover. Install and

tighten all cover bolts to 30 ft-lbs. Make certain no cover bolts are omitted. Use only those bolts
supplied with the enclosure.

3. Reapply power to the station.

Refer to Pub. 42004-723L2 for general information.