2 programming example: preset value, Response from the encoder, Read preset value from the encoder – ifm electronic RM9000 User Manual

Page 12

Advertising
background image

CANopen encoder

12

Index (hex)

Object

0040-005F

manufacturer-specific data types

0060-0FFF

reserved

1000-1FFF

area of the communication profile

2000-5FFF

manufacturer-specific area

6000-9FFF

device-specific area

A000-FFFF

reserved

7.2 Programming example: preset value
The receipt of the SDO answer is to be monitored in the program since the request

is sent permanently without confirmation of receipt�
If a CANopen device is connected to the bus and configured with correct baud rate

and node number, it replies to the bus with a boot up message�
7.2.1 Set preset value (master to encoder with node number 1)
Set preset value (value 1000)

Identifier

DLC

Command

Index

Sub index Service data

NN 1

download

6003h

byte 4

byte 5

byte 6

byte 7

601

8

23h

03h

60h

00h

00h

10h

00h

00h

Response from the encoder

Identifier

DLC

Command

Index

Sub index Service data

NN 1

download

6003h

byte 4

byte 5

byte 6

byte 7

581

8

60h

03h

60h

00h

00h

00h

00h

00h

Read preset value from the encoder

Identifier

DLC

Command

Index

Subindex Service data

NN 1

download

6003h

byte 4

byte 5

byte 6

byte 7

601

8

40h

03h

60h

00h

00h

00h

00h

00h

Response from the encoder

Identifier

DLC

Command

Index

Sub index Service data

NN 1

download

6003h

byte 4

byte 5

byte 6

byte 7

581

8

43h

03h

60h

00h

00h

10h

00h

00h