3 setting of the node number, 1 setting of the node number via sdo objects, 2 setting of the baud rate via sdo objects – ifm electronic RM9000 User Manual

Page 7: 4 bus termination, 4 led indications

Advertising
background image

UK

CANopen encoder

7

5.3 Setting of the node number
5.3.1 Setting of the node number via SDO objects
For devices without terminal cap the address can only be set via SDO objects� The

address of an encoder without terminal cap is set to 32 as standard� Details on

changing the node number → chapter 7.4.
5.3.2 Setting of the baud rate via SDO objects.
For devices without terminal cap the baud rate can only be changed via SDO

objects� The baud rate is set to 125 Kbits/s as default value� Details on changing

the baud rate → chapter 7.4.
5.3.3 Setting the node number and the baud rate via LSS
Another possibility of how to set the node number and the baud rate for encoders

is Layer Setting Services. Further information → chapter 6.3.6.
5.3.4 Bus termination
If the encoder is the last participant, an external terminating resistor or a

terminating T connector has to be used�
5.4 LED indications

LED

Status

Description

red

flashes, 1 Hz

operating voltage OK,

faulty bus connection

red

lights

"BUS OFF" caused e�g� by short circuit, wire

break, faulty connector

green

flashes, 2�5 Hz

operating voltage OK, bus connection OK

green/red

green flashing, 2�5 Hz

and red flashing 1x at each 3rd

pulse of the green LED

guarding error, either node guard or heartbeat

green

flashes, 1 Hz

bus stopped

green

lights

master failure,

encoder remains in the preoperational

operating status

> guard and heartbeat error are not indicated

green/red

green lights/

red flashing, 2�5 Hz

non reproducible indication (no clear

description of the indication)