CANopen encoder

8

6 Configuration

This chapter describes the configuration of the parameters of an absolute encoder

with CANopen interface�
6.1 Operating modes
6.1.1 General information
In the preoperational mode the encoder replies to the CAN bus after sending its

boot up message�
Boot up message: 700 hex + node number (further details in the Communication

Profile chapter 7�3�)

► Change parameters only in the preoperational mode�
This mode decreases the bus load and simplifies the control of the messages sent

and received� It is not possible to send or receive PDO messages in this mode�
6.1.2 Preoperational mode
To set the encoder to the preoperational mode, the master must send the following

message:

Identifier

Byte 0

Byte 1

Description

0 h

80 h

00

NMT PreOp, all nodes

0 h

80 h

NN

NMT PreOp, NN

NN: node number
It is possible to set all nodes (byte 1 = 0) or individual nodes (byte 1 NN) to the

preoperational mode�
6.1.3 Start-operational mode
To set the encoder to the operational mode, the master must send the following

message:

Identifier

Byte 0

Byte 1

Description

0 h

01 h

00

NMT start, all nodes

0 h

01 h

NN

NMT start, NN

NN: node number
It is possible to set all nodes (byte 1 = 0) or individual nodes (byte 1 NN) to the

operational mode�