Operation, On/off and gfci, Startup wizard – Infloor Thermostat 29050 V2 User Manual

Page 2: Wire connections, Mounting the control, Overview of features and display

Advertising
background image

On/Off and GFCI

On/Off and Reset

Pressing will turn the thermostat on or off. This also Resets

the thermostat to clear an error or GFCI fault. See “GFCI Testing” and

“Troubleshooting”.

GFCI Testing

The GFCI (Ground Fault Circuit Interrupter) in this control must be tested when

installation is finished and once each month.

• Make sure the control shows it is Heating. This may require temporarily

increasing the setpoint temperature.

• Press the button. GFCI TRIP should be indicated on the control.

There will also be a click sound, indicating power has been removed from

the floor heating system. If either of these indications fail, turn off the

thermostat and replace it. Do not continue to use.

• To reset the GFCI TRIP, press

on/off

off and back on.

Startup Wizard

This thermostat comes with a “wizard” to help the user through basic setup.

• When first powered up, or upon resetting the factory defaults, the display

will ask to set the year. Adjust the year by pressing

or

and press

OK

.

• Select the month and press

OK

.

• Select the day and press

OK

.

• Set the hour and minutes (format is 12-hour clock but this can be changed

to a 24-hour clock). See Changing Settings Section.

• Select the sensing method (Floor or Air). Default is Floor. See cautions

before using the Air Sensing method. See Changing Settings Section.

• Select a program schedule. The default is called “Normal Day” where it

makes the floor warmer during morning and evening hours. Any of the

schedules can be customized to fit your needs.

• Press

OK

and the thermostat will begin working automatically.

NORMAL DAY

Cycle

WAKE

LEAVE

RETURN

SLEEP

Monday –

Friday

6:00 AM

(6:00)

8:00 AM

(8:00)

5:00 PM

(17:00)

10:00 PM

(22:00)

82 F (27.8 C) 74 F (23.3 C) 82 F (27.8 C) 74 F (23.3 C)

Saturday

7:00 AM

(7:00)

9:00 AM

(9:00)

5:00 PM

(17:00)

11:00 PM

(23:00)

82 F (27.8 C) 74 F (23.3 C) 82 F (27.8 C) 74 F (23.3 C)

Sunday

7:00 AM

(7:00)

9:00 AM

(9:00)

5:00 PM

(17:00)

11:00 PM

(23:00)

82 F (27.8 C) 74 F (23.3 C) 82 F (27.8 C) 74 F (23.3 C)

NOTE: Air Sensing mode default temperatures are 70F and 62F.

WARM ALL NIGHT

Cycle

WAKE

LEAVE

RETURN

SLEEP

Monday –

Friday

--

8:00 AM (8:00) 5:00 PM (17:00)

--

--

74 F (23.3 C)

82 F (27.8 C)

--

Saturday

--

9:00 AM (9:00) 5:00 PM (17:00)

--

--

74 F (23.3 C)

82 F (27.8 C)

--

Sunday

--

9:00 AM (9:00) 5:00 PM (17:00)

--

--

74 F (23.3 C)

82 F (27.8 C)

--

NOTE: Air Sensing mode default temperatures are 70F and 62F.

HOME DURING DAY

Cycle

WAKE

LEAVE RETURN

SLEEP

Monday –

Friday

6:00 AM (6:00)

--

--

10:00 PM (22:00)

82 F (27.8 C)

--

--

74 F (23.3 C)

Saturday

7:00 AM (7:00)

--

--

11:00 PM (23:00)

82 F (27.8 C)

--

--

74 F (23.3 C)

Sunday

7:00 AM (7:00)

--

--

11:00 PM (23:00)

82 F (27.8 C)

--

--

74 F (23.3 C)

NOTE: Air Sensing mode default temperatures are 70F and 62F.

Wire Connections

Match and connect the two wires marked “LINE1(L)” and “LINE2(N)” to the

house power supply wires using the wire nuts provided. Gently tug on the wires

to make sure they are secure, otherwise a wire could come loose and cause

failure. For added security, overwrap the connections with electrical tape.
Match and connect the two wires marked “LOAD1” and “LOAD2” to the power

lead wires from the floor heating system. Secure these wire connections the

same way with the appropriate size wire nut for the number of wire connected.

CAUTION: Make sure the house power supply voltage matches the voltage

rating of the floor heating system. Do not apply 240 VAC to a 120 VAC rated

system. Connecting the wrong voltage may cause overheating and damage

to the system, the control, floor coverings, etc.

Connect the house ground wire to the ground wire(s) from the floor heating

system. If the electrical box is metal, a short length of wire must be secured to

the electrical box from this ground connection.
Insert the ends of the floor sensor wire into the terminals marked “SENSOR” and

snug the screws. It does not matter which wire goes into which terminal

Infloor Relay 29053

version 2 only (Optional)

Read and follow the instructions provided with the 29053 Version 2.
Pull 18 AWG to 24 AWG 2-conductor shielded wire through the wall from the

Infloor Relay location to this control location. This wire may be up 100 feet (30

m) in length. Strip the wire ends 1/8” to 3/16” (3 mm to 4.5 mm) long. If the

ends are stripped longer than this they may short-circuit.
Connect the wire ends into the “BUS” A and B terminals. Make sure the wire in

“A” terminal is connected to an “A” terminal in the Infloor Relay.

Mounting the Control

Carefully press the wires back into the electrical box. Do not use the control to

push them in, as this may cause connections to loosen and possible failure.
Loosen the screw and remove the front module from the power module. Secure

the power module into the electrical box with the mounting screws provided.
Snap the front module onto the power module and tighten the screw. Press the

Screw Cover in place to cover screw.

Operation

Overview of Features and Display

Press a button if the display is dark. This wakes the display backlight.

on/off

GFCI

Test

Setpoint temperature

Floor temperature

Day

Time

Screw Cover

Cover Screw

Front Module

Load 1

Line 1

Line 2

Load 2

Floor Sensor

Connection

Power Module

!

Advertising
This manual is related to the following products: