Materials required, Common questions – Lencore Spectra Classic: Installation and Operations Manual User Manual

Page 13

Advertising
background image

materials required

common questions

Cable shall be 18 gauge,Stranded ,UL Listed, Plenum Rated,
non shielded.

Transformer shall be UL 1411 Listed with an output of 16/18volts.

Fuse shall be UL Listed 3.0 amps installed at each 40va transformer, 125 volts (Max)
rating. Fuse holder shall be UL Listed with same rating. Not required for installations
using 95v a transformers due to built-in circuit breaker.

Wire nuts & caddy clips.

OPTIONAL EQUIPMENT

Ramset or Hilti Gun (for deck installation)
Telescopic Pole (15’ extension)

1

2

3

4

NOTE

Estimate approximately 20’of wire per unit,allowing additional footage for home runs to

transformers and/or other equipment such as CVC’s,Timers, Amplifiers, etc.

Wire can be purchased in full rolls of 1,000 feet. Standard layouts will require that two-

thirds of wire purchased be 2-conductor and the balance of wire pur chased can be two,

four, or six conductor depending on applications used.