B-Series DV-2 Gas Fireplace

Part No. XG0160 - 141231

Installation

Top Vent Venting Runs

For the B-Series DV-2 Top Vent, there are two types of installations:

A) Through-The-Wall Installations and B) Vertical (Through-The-Roof)

Installations.

Through-The-Wall Installations

Before you install any venting, you must determine whether the venting

run will be acceptable. Unacceptable venting can affect the fireplace's

combustion.
The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the from the fireplace flue collar

to the wall flange of the termination. Plot on the Venting Graph (Fig. 8)

or (Fig.8a) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.

B34DV-2

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 108" and the horizontal run to

the wall flange of the vent termination is 180", this would be an accept-

able installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 44" and the horizontal run to

the wall flange of the vent termination is 72", this would be an acceptable

installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 60" and the hori-

zontal run to the wall flange of the vent termination is 144", this would

NOT be an acceptable installation.

Figure 8. B34-DV-2 Top Vent Venting Graph

B38DV-2

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 84" and the horizontal run to

the wall flange of the vent termination is 36", this would be an acceptable

installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 108" and the horizontal run to

the wall flange of the vent termination is 120", this would be an acceptable

installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and the

horizontal run to the wall flange of the vent termination is 84", this would

NOT be an acceptable installation.

Figure 8a. B38-DV-2 Top Vent Venting Graph

NOTES: All dimension lengths for vertical or horizontal runs are

measured from centre of the vent pipe. Venting runs must

fall within the limits set by the venting graph (Fig 8 or 8a).

B34DV-2

B38DV-2

42 7/8”

B

A

18”

C

72”

39 7/8”

A

B

C

Available Top Vent Components

The following venting components are available for the B-Series DV-2

Top Vent:

4" / 7" Venting

A - Termination TO-4 (3" Length)

MTO-4F (3" Length)

B - Stucco Kits

MSR (Stucco Frame)

MOSR (Stucco Can)

BSR ( Brick Can)

C - Flex Sections MFL-1 (12" f/f Section)

MFL-2 (24" f/f Section)

MFL-3 (36" f/f Section)

MFL-4 (48" f/f Section)

D - Rigid

Sections

MEXT-1 (12" mf Section)

MEXT-2 (24" m/f Section)

MEXT-3 (36" m/f Section)

MEXT-4 (48" m/f Section)

E - Elbows MEL-90MM (m/m 90° Elbow)

MEL-90FF (f/f 90° Elbow)

MEL-90FM (f/m 90° Elbow)

MFL-6 (72" f/f Section)

MEXT-6 (72" m/f Section)