Installation – Montigo B34DV User Manual

Page 8

Advertising
background image

Page 8

B-Series DV-2 Gas Fireplace

Part No. XG0160 -141231

PEL

Example 1:
For our shortest venting configuration use components A and E (see

table on page 7).

Figure 9. Typical Top Vent installation. If the 90° elbow is installed

directly on the fireplace, for height to the center of the

termination see chart on page 4.

Horizontal Venting

Figure 10. Typical Top Vent installation. The solid sections can be used

in various combinations to obtain the desired vent run. The

vent run must fall within the limits set by the venting graph.

90° Elbow

MEXT Section

Termination

Example 2:
Rigid sections and an elbow used in conjunction with 3 ft. flex section

(MFL-3) will, when extended in a five foot chase, allow for a maximum

horizontal run of twelve and one-half feet from the centre of the fireplace

to outside wall and a minimum of 7'6" when retracted in opposite direction

(see Figure 11).
"C" flex sections and "D" rigid sections (See table on page 7) may be

used in conjunction with one another to obtain different possible horizontal

length installations, Figure 12.
NOTE: Flex section with no vertical rise must not exceed maximum

horizontal length of 3 feet (see Figure 13). Flex runs over 3 feet must

fall within the limits set by the venting graph, and must have a minimum

vertical rise of 3" per foot of flex.

Figure 11. Extended Installation using a combination of solid and flex

venting. Use the vent graph to determine your allowable

run, then select appropriate components.

Figure 12. Retracted Installation using a combination of solid and flex

venting. Use the vent graph to determine your allowable

run, then select appropriate components.

Figure 13. Horizontal flex installation with no vertical rise.

Installation

36” max.

Flex Section

Hearth

Termination

Exterior

Wall

Advertising
This manual is related to the following products: