Troubleshooting (cont.) – MovinCool CM25 User Manual

Page 55

Advertising
background image

55

TROUBLESHOOTING (cont.)

Condition

Checking Area

Possible

Cause

Remedy

Self-

Diagnostic

Codes

(Wall

mounted

controller)

Buzzer

Pattern

Unit

does

not

operate

at all.

LCD

displays

self-

diagnostic

codes.

E01

Defective RTS1

thermistor

(short or open)

Replace the wall

mounted controller.

To reset: Press

RESET button.

E02

2

Improper RTS2

thermistor

connection

Check connection.

To reset: Press

RESET button.

Defective RTS2

thermistor

(short or open)

Replace RTS2

thermistor.

To reset: Press

RESET button.

E03

2

Loose ODS

thermistor

connection

Check connection.

To reset: Press

RESET button.

Defective ODS

thermistor

(short or open)

Replace ODS

thermistor.

To reset: Press

RESET button.

E04

2

Loose CTS1

thermistor

connection

Check connection.

To reset: Press

RESET button.

Defective CTS1

thermistor

(short or open)

Replace CTS1

thermistor.

To reset: Press

RESET button.

E05

2

Loose CTS2

thermistor

connection

Check connection.

To reset: Press

RESET button.

Defective CTS2

thermistor

(short or open)

Replace CTS2

thermistor.

To reset: Press

RESET button.

Advertising