Nortec OnLine GSTC User Manual

Page 12

Advertising
background image

8 | Installation

Table 2: Status Screen Variables - CONTINUED

Variable Name

Displayed Information

Description

Product LIne

GSTC

SETC

Service Indicator

On/Off Lamp

Indicator

Provides current service status. The yellow

service light is lit when service is due.

X

X

Software Version

Numerical Chart Item

Indicates the software version installed on the

Humidifiers mainboard.

X

X

Steam Production

On/Off Animated

Indicates that the humidifier is producing steam

in response to a demand signal.

X

X

System Demand
Correct Output

0-100% Numerical Data

Displays the humidifier's current demand

output

X

X

Unit Address

Mailing Address Chart

Item

Provides details on the Humidifier's location.

X

X

Unit Model

Unit Identifier Chart Item

Indicates the model type & size of the selected

humidifier.

X

X

Unit Status

On/Off Lamp

Indicator

Indicates if unit has responded to a demand

signal. The green LED is on when a demand

signal is present.

X

X

Water Level High

On/Off Lamp

Indicator

Yellow light is on if water is at a high level. Light

combinations are possible for mid-state water

levels.

X

X

Water Level Mid-
Range

On/Off Lamp Indicator

Green light is on if water is at optimal level.

Light combinations are possible for mid-state

water levels

X

X

Water Level Low

On/Off Lamp Indicator

Red light is on if water is at a low level. Light

combinations are possible for mid-state water

levels.

X

X

Weighted Hours

Hours Chart Item

Equivalent operating hours convoluted to 100%

steam production. Ex. Weighted hours = 2

hours at 50% demand.

X

X

Manual Drain

On/Off Chart Item

Drain unit when “on”.

X

X

Pre-Clean

On/Off Chart Item

Initiates a pre-clean cycle.

X

X

Power Reset

On/Off Chart Item

Performs a software reset similar to turning the

unit off and then on again.

0: Standalone unit (default setting)

1: Unit is Master

X

X

Multimode

Status Item

2: Unit is Slave

Lists current signal type the unit is configured

for

0: 0-5Vdc
1: 1-5Vdc

2: 0-10Vdc
3: 2-10Vdc
4: 0-16Vdc

5: 3.2-16Vdc

6: 0-10mA

X

X