Nortec LINKS 2 NHRS User Manual

Page 19

Advertising
background image

Installation | 15

Table 4: Variable Definitions

Variable Name

Description

Type

Range

Unit

R/W

Details

nviRHDem_x

Write RH or
Demand signal value
to humidifier

Analog
Value

0 - 100

%

Write

Requires network controls
(nviNetSensor = 1)

nviSet_x

Writes the desired
space setpoint when
using sensor controls

Analog
Value

30 - 95

%

Write

Use only when sending RH
value to RHDem

nviCapLimit_x

Set a manual
capacity restriction
for the humidifier

Analog
Value

50 - 100

%

Write

Limits output to percentage
of total capacity

nvoRHDem_x

Read RH or Demand
signal value from
humidifier

Analog
Value

0 - 100

%

Read

Used with hardwired or
network control signal

nvoSet_x

Read space setpoint
(sensor type controls
only)

Analog
Value

30 - 95

%

Read

Sensor controls only, not for
demand type controls

nvoCapLimit_x

Reads the manual
capacity restriction
for humidifier

Analog
Value

50 - 100

%

Read

Adjust using writeable
nviCapLimit variable

nvoSysDemand_x

Read system ouput /
demand

Analog
Value

0 - 100

%

Read

Displays output as
percentage of capacity

nvoHourOpt_x

Read operation
hours of unit

Analog
Value

0 -
Infinity

hrs

Read

Displays cumulative hours
since startup

nvoSmallHrs_x

Read minor
maintenance hours
remaining

Analog
Value

0 - 6000

hrs

Read

Displays hours until next
minor maintenance

nvoLargeHrs_x

Read major
maintenance hours
remaining

Analog
Value

0 - 6000

hrs

Read

Displays hours until next
major maintenance

nviNetSensor_x

Switches between
hard wired or
network control
signal

Binary Value 0,1

-

Write

1 = Use Modbus to write
sensor or demand value
0 = Hard wired sensor or
wired demand signal

nvoNetSensor_x

Confirms humidifier
control mode

Binary Value 0,1

-

Read

1 = Use Modbus to write
sensor or demand value
0 = Hard wired sensor or
wired demand signal

nvoStatus_x

Read humidification
status

Binary Value 0,1

-

Read

0 = Idle / Standby
1 = Active / Humidifying

nvoService_x

Read service warning
status

Binary Value 0,1

-

Read

0 = No Service Warning
1 = Service Required

nvoFault_x

Read fault status

Binary Value 0,1

-

Read

0 = No Fault
1 = Fault Detected

nvoInputType_x

Read control signal
mode

Binary Value 0,1

-

Read

0 = Demand Signal
1 = RH Sensor Signal
("Transducer Control")

nvoConnection_x

Read communication
status

Binary Value 0,1

-

Read

0 = Communication Error
1 = Normal Communications