Nortec LINKS 2 NHRS User Manual

Page 20

Advertising
background image

16 | Installation

Table 5: Humidifier Variable Addresses

BACnet

LonWorks

N2

Variables

Data

Type

Object

ID

SNVT Type

SNVT
Index

Data Type

Address

Unit 1 Variable Name

nviRHDem_1

AV 1

SNVT_lev_percent

1

Analog Output

1

nviSet_1

AV 2

SNVT_lev_percent

2

Analog Output

2

nviCapLimit_1

AV 3

SNVT_lev_percent

3

Analog Output

3

Not Used

AV 4

SNVT_lev_percent

4

Analog Output

4

Not Used

AV 5

SNVT_lev_percent

5

Analog Output

5

nvoRHDem_1

AV 6

SNVT_lev_percent

6

Analog Input

6

nvoSet_1

AV 7

SNVT_lev_percent

7

Analog Input

7

nvoCapLimit_1

AV 8

SNVT_time_hour

8

Analog Input

8

nvoSysDemand_1

AV 9

SNVT_time_hour

9

Analog Input

9

nvoHourOpt_1

AV 10

SNVT_time_hour

10

Analog Input

10

nvoSmallHrs_1

AV 11

SNVT_time_hour

11

Analog Input

11

nvoLargeHrs_1

AV 12

SNVT_lev_percent

12

Analog Input

12

Not Used

AV 13

SNVT_lev_percent

13

Analog Input

13

Not Used

AV 14

SNVT_lev_percent

14

Analog Input

14

Not Used

AV 15

SNVT_lev_percent

15

Analog Input

15

nviNetSensor_1

BV 1

SNVT_switch

16

Digital Output

1

Not Used

BV 2

SNVT_switch

17

Digital Output

2

Not Used

BV 3

SNVT_switch

18

Digital Output

3

nvoNetSensor_1

BV 4

SNVT_switch

19

Digital Input

4

nvoStatus_1

BV 5

SNVT_switch

20

Digital Input

5

nvoService_1

BV 6

SNVT_switch

21

Digital Input

6

nvoFault_1

BV 7

SNVT_switch

22

Digital Input

7

nvoInputType_1

BV 8

SNVT_switch

23

Digital Input

8

nvoConnection_1

BV 9

SNVT_switch

24

Digital Input

9

Not Used

BV 10

SNVT_switch

25

Digital Input

10

Not Used

BV 11

SNVT_switch

26

Digital Input

11

Not Used

BV 12

SNVT_switch

27

Digital Input

12

Not Used

BV 13

SNVT_switch

28

Digital Input

13

Not Used

BV 14

SNVT_switch

29

Digital Input

14

Not Used

BV 15

SNVT_switch

30

Digital Input

15

Advertising