Nortec LINKS 2 NHRS User Manual

Page 22

Advertising
background image

18 | Installation

Table 5: Humidifier Variable Addresses - CONTINUED

BACnet

Lonworks

N2

Variables

Data

Type

Object

ID

SNVT Type

SNVT
Index

Data Type

Address

Unit 3 Variable Name

nviRHDem_3

AV 31

SNVT_lev_percent

61

Analog Output

31

nviSet_3

AV 32

SNVT_lev_percent

62

Analog Output

32

nviCapLimit_3

AV 33

SNVT_lev_percent

63

Analog Output

33

Not Used

AV 34

SNVT_lev_percent

64

Analog Output

34

Not Used

AV 35

SNVT_lev_percent

65

Analog Output

35

nvoRHDem_3

AV 36

SNVT_lev_percent

66

Analog Input

36

nvoSet_3

AV 37

SNVT_lev_percent

67

Analog Input

37

nvoCapLimit_3

AV 38

SNVT_time_hour

68

Analog Input

38

nvoSysDemand_3

AV 39

SNVT_time_hour

69

Analog Input

39

nvoHourOpt_3

AV 40

SNVT_time_hour

70

Analog Input

40

nvoSmallHrs_3

AV 41

SNVT_time_hour

71

Analog Input

41

nvoLargeHrs_3

AV 42

SNVT_lev_percent

72

Analog Input

42

Not Used

AV 43

SNVT_lev_percent

73

Analog Input

43

Not Used

AV 44

SNVT_lev_percent

74

Analog Input

44

Not Used

AV 45

SNVT_lev_percent

75

Analog Input

45

nviNetSensor_3

BV 31

SNVT_switch

76

Digital Output

31

Not Used

BV 32

SNVT_switch

77

Digital Output

32

Not Used

BV 33

SNVT_switch

78

Digital Output

33

nvoNetSensor_3

BV 34

SNVT_switch

79

Digital Input

34

nvoStatus_3

BV 35

SNVT_switch

80

Digital Input

35

nvoService_3

BV 36

SNVT_switch

81

Digital Input

36

nvoFault_3

BV 37

SNVT_switch

82

Digital Input

37

nvoInputType_3

BV 38

SNVT_switch

83

Digital Input

38

nvoConnection_3

BV 39

SNVT_switch

84

Digital Input

39

Not Used

BV 40

SNVT_switch

85

Digital Input

40

Not Used

BV 41

SNVT_switch

86

Digital Input

41

Not Used

BV 42

SNVT_switch

87

Digital Input

42

Not Used

BV 43

SNVT_switch

88

Digital Input

43

Not Used

BV 44

SNVT_switch

89

Digital Input

44

Not Used

BV 45

SNVT_switch

90

Digital Input

45


Advertising
This manual is related to the following products: