Plumbing – Nortec Blower Packs User Manual

Page 13

Advertising
background image

Blower Pack Installation Guide | 10

Plumbing

RM-BP Plumbing consists of steam and condensate line connections located at the bottom of the
blower pack. The steam line connection is of size 1.75” OD. The Blower Pack is designed to work
for up to 100lbs/hr. Ensure that the steam inlet on the bottom of the blower pack is unobstructed.

Figure 8. Plumbing Connections

Use Nortec Hose to connect to RM-BP steam inlet. A hose gear clamp can be used to ensure

tight fit. DO NOT OVERTIGHTEN the gear clamp.

The Condensate line should not terminate in a sink used frequently by personnel, or where

plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons.

Insure condensate line is adequately sized to provide free and easy draining and that an air gap

is installed as shown

Do not use hose other than Nortec Hose, See Table 1 for plumbing recommendations.

Advertising