Blower Pack Installation Guide | 16

5.

Install traps on condensate lines at least 3 feet. (0.9m) below connection, ensure P trap
3 inches height

A condensate trap must be installed at least 3 ft (1 m) below the condensate outlet on the blower
pack to prevent steam from escaping. Trap depth must be equal or more than 3” (76 mm).

6.

Do not combine NH-EL steam lines before RM-BP