Nortec MLP RO pump station User Manual

Page 12

Advertising
background image




TI071GB-02 /06.11.09/LJ 12/12

3*FLU xx.x - FLOW xx

FLU -The minimum time during
which the section humidifies to ensure
exchange of water in the hoses. The
operation time is set in minutes per 30
minutes.
FLOW - The capacity in the section -
in liter per hour

0-2,0




0-1000

0,2




50

4*PRO xx - PER xx.x

PRO - Proportional belt for humidity
regulation of the section
PER -The period (a pulse & and a
pause) in the section indicated in
seconds.

0-50

10-1000

20

60,0

4*MON xx.x -PAU xx.x

MON- The lowest pulse time during
which can be humidfied in the section.
(If the calculated time is less, the time
is added to the calculation for the next
period). Time is indicated in seconds.
PAU -The time of the forced pause
that minimum is held in each period.
The time is indicated in seconds.

0-50,0





1-200,0

5,0





10,0

4*FLU xx.x - FLOW xx

FLU -The minimum time during
which the section humidifies to ensure
exchange of water in the hoses. The
operation time is set in minutes per 30
minutes.
FLOW - The capacity in the section -
in liter per hour

0-2,0




0-1000

0,2




50


Reset

to standard values

All settings can be reset to standard settings by pressing emergency stop for at least 10
seconds.
Then the emergency stop is loosened while the red reset key is pressed, the display writes
after approx. 5 sec. INITIALIZING. Then you can release the reset key

Advertising