AcquiSuite route mapping display

The AcquiSuite data acquisition server has additional diagnostic features that assist with ModHopper deployments. The
most useful is the ModHopper route map. Select the ModHoppers menu from the Wireless section in the AcquiSuite menu
tree as shown below.

The graph will draw a blue box for each ModHopper that is attached to the system. The blue number inside the box icon is
the Modbus address of the ModHopper. To the side of each icon, three lines of information will be shown.

The device list name will be shown to the side of each ModHopper icon

The link quality, hops and round trip time (rtt) will be printed under the ModHopper name.

A list of attached Modbus device addresses will be shown on the third line. This is a list of addresses that the
ModHopper has automatically detected on the local RS485 port.

The graph will print strong links in thick green lines. Lines progress from green, to yellow, to red to indicate weak links.