Obvius R9120 Rev C User Manual

Page 13

Advertising
background image

offset point type desc

------- ------- ------- ------------------

118 40119 UINT16 RF BadChecksum packets

119 40120 UINT16 RS485 BadChecksum packets

120 40121 UINT16 RF RX Good packets

121 40122 UINT16 RS485 RX Good packets

122 40123 UINT16 RF TX packets

123 40124 UINT16 RS485 T Good packets

124 40125 UINT16 RF TX resend packets

125 40126 UINT16 RS485 TX resend packets

126 40127 UINT16 RF RouteChange packets

127 40128 UINT16 RS485 RouteChange packets

128 40129 UINT16 Number of known nodes. (including ourselves)

129 40130 UINT16 Our modbus address

130 40131 UINT16 R9120 Hardware Version (0=rev-A, 1=rev-B, etc)

131 40132 UINT16 Model number bytes 1,2 (4 registers = 8 char string)

132 40133 UINT16 Model number bytes 3,4 (4 registers = 8 char string)

133 40134 UINT16 Model number bytes 5,6 (4 registers = 8 char string)

134 40135 UINT16 Model number bytes 7,8 (4 registers = 8 char string)

135 40136 UINT16 Radio Serial MSW

136 40137 UINT16 Radio Serial LSW

137 40138 UINT16 Radio Firmware

138 40139 UINT16 Radio Type 1=R9120-1(lowpower), 2=R9120-3(highpower)

0=unknown)

139 40140 UINT16 (R/W) Modbus 485 timeout in ms. Default 240ms range 40max

to 2000ms. Affects modhopper in master mode only.

(max 5000ms in v1.17)

140 40141 UINT16 (R/W) Pulse KYZ flag bitmap. 0x01 = pulse1 kyz mode,

0x02 = p2, etc.

141 40142 UINT16 Reserved

142 40143 UINT16 (R/W) RS485 force master/slave modes. 0=auto/default,

1=force-master, 2=force-slave. (firmware 1.17 or later)

143 40144 UINT16 RS485 master/slave mode status. 0=master, 1=slave.

(firmware 1.17 or later)

144 40145 UINT16 RS485 baud rate. 2=9600, 3=19200. (firmware 1.17 or

later)

145 40146 UINT16 (R/W) contact closure threshold. in ohms. 100-2550 ohms

allowed. (rev-c only, firmware 2.02 or later)

146 40147 UINT16 (R/W) contact closure speed, pulse speed: 0=10Hz/default,

1=50Hz, 2=100Hz, 3=250Hz (firmware 2.02 or later)

147 40148 UINT16 power supply voltage monitor (rev-c only) scale: x100

148 40149 UINT16 pcb temperature monitor (rev-c only) scale: x100

149 40150 UINT16 400MHz RX Good packet count (rev-c only)

150 40151 UINT16 400MHz RX Bad packet count (rev-c only)

151 40152 UINT16 (R/W) minimum packet time, how frequent to save sensor data

packets. (10-2550 seconds) (firmware 2.02 or later)

152 40153 UINT16 RS485 serial port option:(firmware 2.05 or later)

bits 0-1: 0=N, 1=E, 2=O

bit 2: 0=8bit, 1=7bit

bit 3: 0=1stop, 1=2stop

Note: read only, always returns 8N1