Ethernet communication module dvpen01-sl – Delta DVPEN01-SL User Manual

Page 15

Advertising
background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

13

C R # 2 5 1 :

Error Code

Explanations:

Table of error code:

Bit No.

Error

b0

The network is not yet connected.

b1

Incorrect IP setting

b2

CR#13 is set as “transmitting data”, but the data exchange

is forbidden.

b3

CR#13 is set as “transmitting data”, but the data exchange

mode has not yet been enabled.

b4 NTP-Server

connection

fails.

b7

SMTP-Server connection fails.

b8

DHCP has not obtained the correct network parameter.

„

RTU Mapping

C R # 1 5 :

Enabling Flag for RTU Mapping

Explanations:

1: Enable; 0: Disable. Default = 0

Firmware V2.0 and later versions support RTU mapping.

C R # 1 6 :

Connection Status of RTU Mapping Slave

Explanations

:

b3 ~ b0 display the connection status of RTU slave. The connection may encounter some

problems when any of the bits becomes 0. Firmware V2.0 and later versions support RTU

mapping.

b0: Status of RTU slave 1
b1: Status of RTU slave 2
b2: Status of RTU slave 3
b3: Status of RTU slave 4

4.3 Numbering of Left-Side Modules

After DVPEN01-SL is installed properly, you need to compile the PLC program to control the special I/O

module. PLC offers FROM instruction (for reading) and TO instruction (for writing) to control the control registers

(CR) in the special I/O module.

Numbering of the modules: Every special I/O module connected to PLC MPU has a No. to allow you to know

which module is which when compiling the PLC program. The first special I/O module attached at the left hand

side of the PLC MPU is numbered as K100, the second as K101, the third K102, and so on.

Advertising