Ethernet communication module dvpen01-sl – Delta DVPEN01-SL User Manual

Page 53

Advertising
background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

51

END

M1013

K100

K1

K100

K100

K1

M2

M1

M1

SET

M1

TOP

K28

TOP

TOP

K100

TOP

SET

M2

M1

RST

K100

K1

M2

K14

D14

RST

M2

RST

M2

= D14 K2

= D14 K3

FROM

K1

K100

K1

TOP

K100

TOP

K1

K1

K0

K0

K26

K25

K29

K14

K13

D100

K7

H4

HC0A8

D100

T D

R

M1000

Explanations:

The data exchange will be executed every one second.

Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination

PLC.

Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 =

H’C0A8) should be written into CR#26, and the last two IP codes (0.4 = H’0004) into CR#25.

Write the data in RTC into CR#29 ~ CR#35.

Write “1” into CR#13 to start the data exchange.

CR#14 = 2 refers to successful execution. CR#14 = 3 refers to failed execution.

2. Compile the ladder diagram for PLC_A and download it to PLC_A.

END

M1013

K7

D0

K49

K100

FROM

Explanations:

The received data are stored in CR#49 ~ CR#55.

The data received every one second are written into D0 ~ D6.