Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

45

4. Switch to “Select Recipients” page. Check all the boxes of “Recipient 1”. Click on “OK” to complete

the setting.

5. After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and

download it to the MPU. See below for the program design:

END

X0

T0

K100

K3

K1

K4

K5

K6

K1

X0

T0

K100

K1

K1

T0

K100

K1

K1

T0

K100

K1

K1

Y0

Y0

Explanations:

If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of

DVPEN01-SL, and the first E-Mail will be sent out.

If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of

DVPEN01-SL, and the second E-Mail will be sent out.

If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of

DVPEN01-SL, and the third E-Mail will be sent out.

If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of

DVPEN01-SL, and the fourth E-Mail will be sent out.

6.8 Application of Data Exchange (1)

Application

Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A

Network
requirement

(1) Adopting static IP.
(2) IP of PLC_A: 192.168.0.4
(3) IP of PLC_B: 192.168.0.5”
(4) Update from PLC_B to PLC_A