Ethernet communication module dvpen01-sl – Delta DVPEN01-SL User Manual

Page 49

Advertising
background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

47

END

M1013

K100

K1

K1

K100

K100

K1

M2

M1

M1

SET

M1

TOP

K28

TOP

TOP

K29

K14

K13

K0

D100

K7

K100

K1

TOP

K1

SET

M2

M1

RST

K100

K1

M2

K14

D14

RST

M2

RST

M2

= D14 K2

= D14 K3

FROM

D100

T D

R

M1000

Explanations:

The data exchange will be executed every one second.

Write the communication address of the destination PLC in CR#28, and DVPEN01-SL will

automatically detect by the previous setting that No. 1 IP is “192.168.0.4".

Write the data in RTC into CR#29 ~ CR#35.

Write “1” into CR#13 to start the data exchange.

CR#14 = 2 refers to successful exchange. CR#14 = 3 refers to failed exchange.

5. Compile the ladder diagram for PLC_A and download it to PLC_A.

END

M1013

K7

D0

K49

K100

FROM

Explanations:

The received data are stored in CR#49 ~ CR#55.

The data received every one second are written into D0 ~ D6.