Ethernet communication module dvpen01-sl, 6 application examples – Delta DVPEN01-SL User Manual

Page 32

Advertising
background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Operation Manual

30

Check “Default Setting” box and click on “Yes”.

Note:

If you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether

the password is locked or not. It takes approximately 10 seconds to return to default setting,

so DO NOT switch off the power within the 10 seconds.

6 Application

Examples

6.1 Setting up IP and Communicating through WPLSoft

Application

Setting up network parameters of DVPEN01-SL directly on the PC.

Network
requirement

(1) IP of PC executing WPLSoft: 192.168.0.3
(2) Subnet mask: 255.255.255.0; Gateway: 192.168.0.1
(3) IP of DVPEN01-SL: 192.168.0.4
(4) Connect the PC and DVPEN01-SL by RJ-45 cable.
Note:

Both PC and DVPEN01-SL have to adopt static IP.

1. The connection

PC

DVP-PLC

DVPEN01

2. Open "Communication Setting” in WPLSoft.