Online power, Torque value – OnLine Power Telecommunication User Manual

Page 10

Advertising
background image

i

OnLine Power

TORQUE VALUE

TERMINAL or BOLT

TORQUE

IN/LBS. N-METER

DEAD FRONT PANEL

49.60

5.61

TB1 18.0

2.03

TB2 18.0

2.03

ELECTRONIC TRAY GROUND

14.16

1.6

TRAY TO CABINET SCREW

49.6

5.61

CIRCUIT BREAKER, TERMINALS 27.0

3.0

SURGE PROTECTOR

25.48

2.88

CONDUIT INLET COVER PLATE

OVER TORQUE WILL DAMAGE THE GASKET

18.24 2.08

BATTERY CONNECTIONS

68.17

7.7

DOOR GND

49.60

5.61

GROUND LUGS, ON OUTSIDE

49.60

5.61

PAD MOUNTING BRACKET

84.96

9.6

This unit was designed for specific applications. It should not be modified and/or used for any application
other than for that which it was designed. Optional equipment not described in the sales literature or this
manual should not be installed without first checking with the Service department. If you have any
questions about this unit’s application call the Service department at the number shown on the page f.