3-2

(e) It is necessary to guarantee the temperature and humidity values of the site

into which the ELI will be installed. These should be within the range
allowed by the specification. The ELI is capable of continuous normal
operation within a temperature range of 0°(32°) to 40° (104°). For optimal
performance and reliability, and to prolong lifetime, it is recommended to
keep the environment temperature below 25°, and humidity below 80%.

(f) If the ELI is installed outdoors, avoid direct exposure of the ELI to the

sunlight, wind, and rain. Avoid any exposure to sand or dust.

(g) The floor loading capacity should be high enough to endure the weight of the

ELI. The ELI is mounted on four right -angled steel angles. Insert
corresponding bolts and nuts (dia. 1/2”) into the floor for securing the ELI
on the floor when it is located in an area where earthquakes is possible, or
where motion may occur, e.g. vehicle mounted. Layout dimensions are shown
below.