6005-145 Rev. A

9-5

9.4.2

Periodic Testing of unit

The unit should be manually exercised on a periodic basis (once every three
months, for example). This forces the unit to transfer to the battery and return to
main power. This process activates self-diagnostic testing, which may reveal
conditions that require attention.

9.4.3

Maintaining the Batteries


































Danger!

THE BATTERY CIRCUIT BREAKER OPERATES AT THE RATED BATTERY
VOLTAGES AT ALL TIMES. A TRIPPED BATTERY CIRCUIT BREAKER
INDICATES A SERIOUS PROBLEM THAT MAY RESULT IN SERIOUS INJURY
OR DAMAGE TO THE EQUIPMENT; DO NOT CLOSE THE CIRCUIT BREAKER
WITHOUT KNOWING WHY IT FAILED. CHECK FOR A SHORT IN BATTERY OR
CONNECTIONS. CALL ONLINE POWER CUSTOMER SERVICE AND SUPPORT
FOR ASSISTANCE AT 1-800-PWR-SRVC.

Danger!

THE BATTERY ELECTROLYTE IS A DILUTED SULFURIC ACID THAT IS
HARMFUL TO THE SKIN AND EYES. IT IS ELECTRICALLY CONDUCTIVE AND
CORROSIVE. WEAR FULL EYE AND HAND PROTECTION ALONG WITH
PROTECTIVE CLOTHING. IF THE ELECTROLYTE CONTACTS THE SKIN,
WASH IT OFF IMMEDIATELY WITH WATER. IF ELECTROLYE CONTACTS
THE EYES, FLUSH THOROUGHLY AND IMMEDIATELY WITH WATER. SEEK
IMMEDIATE MEDICAL ATTENTION. SPILLED ELECTROLYTE SHOULD
ADDRESSED

PER

APPROPRITE

HARADIDEROUS

SPILL

CLEANUP

PROCEDURES.

Danger!

DO NOT DISPOSE OF A BATTERY OR BATTERIES IN A FIRE.
THE BATTERIES MAY EXPLODE CAUSING DEATH OR SERIOUS INJURY.