Battery Cabinets

Although the individual batteries are sealed and require minimal maintenance only, the
batteries should be given a periodic inspection and electrical check every six months.

Battery Service Agreements are available through OnLine Power Customer Service and
Support at 1-800-PWR-SRVC (800-797-7782).

In order to qualify for battery warranty replacement, you will need to show records of the
battery maintenance history including battery numbers, battery voltages (individual cells),
terminal torque measurements and dates of maintenance.

9.4.5

Power Connections

Check for corrosion and connection integrity. Visually inspect wiring for discolored or

cracked insulation. Clean and / or re-torque as required.

All Battery terminal connections must be tighten with proper torque value set in

accordance with the table or instructions provided by battery manufacturer.

Use the correct torque tool to tighten the terminal bolts as indicated in table below and

use all hardware's provided with batteries.

Type – Standard VRLA Battery

Battery part number

Initial torque in LBS

Annual re-torque in LBS

Terminal Type

Hardware

PRC-12150 C

(150AH)

120 IN-LB / 13.6 NM

115 IN-LB / 13.6 NM

Copper Insert

Terminal

¼ - 20 UNC Bolt

UB 12750

88.5 IN-LB / 10 NM

84 IN-LB / 9.5 NM

Z1 "Z" post

type terminal

1 to 1.25" long bolt

w/14mm head, 14mm nut,

8mm washer & lockwasher

UB12900

88.5 IN-LB / 10 NM

84 IN-LB / 9.5 NM

Same as above

Same as above

UB12110

88.5 IN-LB / 10 NM

84 IN-LB / 9.5 NM

Same as above

Same as above

Type G – Longer warranty battery

Battery part number

Initial torque in LBS

Annual re-torque in LBS

Terminal Type

Hardware

GSLF – 10512

120 IN-LB / 13.6 NM

115 IN-LB / 13.0 NM

Copper Insert

¼ "

GSLF - 12012

120 IN-LB / 13.6 NM

115 IN-LB / 13.0 NM

Copper Insert

¼ "

Type N – Nickel-Cad battery

(only nickel plated copper cable lugs should be used).

Ni-Cad P/N

Recommended Torque

Bolt Diameter

BM 112/ 138

66 IN-LB

7.5 NM

M5

BM 148/ 184

177 IN-LB

20 NM

M8

BM 195/231/277

266 IN-LB

30 NM

M10

NOTE: For annual re-torque; reduce 5 IN-LB from recommended torque value.

CAUTION: Torque all connections in accordance with the above tables unless provided from battery

manufacturer. Failure to do so may create an unsafe condition or fire hazard.