OnLine Power Signal Saver IPC User Manual

Page 43

Advertising
background image


6002-1842 Rev A ECO# 8881

33

2.2.4 Start

up

Purpose: Describes the Start Up procedure.



Within 30 seconds or less depending

on line qualify time setting, the LCD
display Changes to "ON LINE", The
Green Output LED is lit indicating
input power to be within acceptable
frequency and voltage range and the
output is powered
from Utility

Turn ON the Battery Circuit Breaker

The LCD display shows STANDBY

Verify that the AC input & output

and Battery Circuit Breaker on
the BBS is OFF

Turn ON AC input & output
Circuit Breaker

Turn ON the upstream

Utility input Circuit Breaker
if it is not already ON

Verify the load has power

Place the Manual Bypass Switch
in MBS/PTR assy in BBS position

START

START UP FINISHED

Observe the RED ALARM LED, if it
is ON or FLASHING. follow the
troubleshooting sequence as below:

1 Investigate the alarm

2 Perform a self-test with the
load (s) connected
3 if unit passes the self test
Verify that loads are operating
normally
4 See the troubleshooting table
in the
BBS2000 Manual section 2.4.3
5 Contact Online Power Customer
Service

WARNING:

Never run the BBS when it is overloaded. Damage
to the inverter, batteries or unexpected shutdowns
may result. If the unit detects a load greater than
2000 VA, it will automatically shut down after 3
minutes.

Advertising