Start Up and Commissioning

General

In order to have a trouble free start-up, it is important to follow a few
simple procedures. Before applying power for the fi rst time, it is very
important to run through a few simple checks.

One of the most important checks to make before powering up the system
for the fi rst time is to make sure that the VCM-X Modular or VCM-X
Modular E-BUS Controller is confi gured properly for your application.
Refer to the VCM-X Controller Technical Guide or VCM-X Modular
E-BUS Controller Technical Guide
for more information. A handheld
Modular Service Tool, Modular System Manager, or System Manager
Touch Screen connected to the VCM-X Modular or VCM-X Modular
E-BUS Controller will allow you to confi gure your application. Refer to
the VCM-X Operator’s Interfaces Technical Guide or System Manager
TS Technical Guide
for more information.

Check all wiring leads at the terminal block for tightness. Be sure that
wire strands do not stick out and touch adjacent terminals. Confi rm
that all sensors required for your system are mounted in the appropriate
location and wired into the correct terminals.

WARNING: Observe polarity! All boards must be wired

GND-to-GND and 24 VAC-to-VAC. Failure to

observe polarity could result in damage to the

boards.

Table 1: Unit Confi gurations Chart

UNIT CONFIGURATIONS

PERMUTATION

SYSTEM A

SYSTEM B

HARDWARE

VCM-X WSHP

CONFIGURATION

Comp A1

Comp A2 Comp B1

Comp B2

Relay 1

Relay 2

Relay 3

Relay 4

1

On/Off

On/Off

Use VCM-X Modular

Series Controller Only

2 Compressors

2

Digital

On/Off

Use VCM-X Modular

Series Controller Only

2 Compressors
Digital Compressor

3

Digital

Digital

Use VCM-X Modular

Series Controller and

Full Digital Module

2 Compressors
Full Digital

4

On/Off

On/Off

On/Off

On/Off

Use VCM-X Modular

Series Controller Only

4 Compressors

5

Digital

On/Off

On/Off

On/Off

Not Available

Not Available

6

Digital

On/Off

Digital

On/Off

Use VCM-X Modular

Series Controller Only

4 Compressors
Digital Compressor

7

Digital

Digital

Digital

Digital

Use VCM-X Modular

Series Controller and

Full Digital Module

4 Compressors
Full Digital

In the Cooling Mode, the Compressors will stage in the following order:

Permutations 1, 2 & 3: Compressor A1 -> Compressor A2
Permutations 4: Compressor A1 -> Compressor B1 -> Compressor A2 -> Compressor B2
Permutations 6: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2
Permutations 7: Compressor A1 & Compressor B1 -> Compressor A2 & Compressor B2

In the Dehumidifi cation Mode, the Compressors will stage in the following order:

Permutation 4: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2

All other permutations in the Dehumidifi cation Mode stage as described in the Cooling Mode.