Installation and wiring, Technical guide full digital module 9, All comm loop wiring is straight thru – Orion System Full Digital Module User Manual

Page 9: T to t, r to r & shld to shld, 24vac gnd, G - fan on/off only r - 24vac

Advertising
background image

Technical Guide

Full Digital Module

9

Installation and Wiring

WARNING: Be sure all controllers and modules are

powered down before connecting or

disconnecting HSSC cables.

Figure 5, cont.: VCM-X E-BUS Controller to Full Digital Module Wiring Diagram

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual

Component Wiring

Diagrams For

Detailed Wiring Of
Analog Inputs And

For Stand Alone Applications,

Connect To System Manager. For Network

Applications Connect To Next Controller

And/Or MiniLink PD On Local Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Contacts
R2 Through R5 May Be User-Configured
For The Following:
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat
Note: 1.) When Using the HP2C Module,
All Compressors Will Be Wired From the
Protection Module, Not the VCM-X Controller.
Note: A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To
Expansion Module(s)
(When Used)

Connect To Digital Room Sensor And/Or
Digital CO Sensor

2

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For Correct
Total Load.
VCM-X Modular Controller = 8

OE332-23E-VCMX-MOD-A

VCM-X Modular

E-BUS Controller

Note:
All Relay Outputs Are Normally Open And
Rated For 24 VAC Power Only.
1 Amp Maximum Load.

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers

HSSC Cable Connect To

VCM-X E-BUS Port

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY
COMMON

IC DIGITAL

SENSOR

2

IC

EXPANSION

2

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

ANALOG INPUT

JUMPER

SETTINGS

WattMaster Label

#LB102073-01-A

Rev.: 1A

www.aaon.com

www.orioncontrols.com

VCM-X MODULAR E-BUS CONTROLLER

Orion No.:OE332-23E-VCMX-MOD-A

AAON No.:

V07150

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

AI7

A01

A02

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST

OR VOLTAGE RESET SOURCE

= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)

LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MODULE ALARM

4

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP COOL FAIL

3

4

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

ZONE OVR

2

5

OUTPUT FORCE ACTIVE

0

6

E-BUS

CONNECTOR

Advertising