Installation and wiring, Full digital module technical guide 6 – Orion System Full Digital Module User Manual

Page 6

Advertising
background image

Full Digital Module

Technical Guide

6

Connect To

E-BUS

Distribution

Module

Line Voltage

24 VAC

GND

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual Component

Wiring Diagrams For

Detailed Wiring Of Analog

Inputs And Outputs

For Stand Alone Applications,
Connect To System Manager.

For Network Applications

Connect To Next Controller

And/Or MiniLink PD On Local Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Contacts
R2 Through R5 May Be User-Configured
For The Following:
1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat
Note: 1.) When Using the HP2C Module,
All Compressors Will Be Wired From the
Protection Module, Not the VCM-X
Controller.
2.) A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User-
Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To E-BUS Distribution Module
or Expansion Module(s) (When Used)

Connect To Digital Room Sensor And/Or
Digital CO Sensor

2

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For
Correct Total Load.
VCM-X Modular Controller
= 8 VA

OE332-23-VCMX-MOD-A

VCM-X Modular Controller

Note:
All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers

Figure 4: VCM-X Modular Controller Connection to Full Digital Module

Installation and Wiring

VCM-X Modular Controller to Full

Digital Module Wiring

When using the VCM-X Modular Controller, the E-BUS Distribution
Module is required ot connect to the Full Digital Module. The Full Digital
Module connects to the E-BUS Distribution Module using a modular
HSSC cable. The Full Digital Module requires a 24 VAC power con-
nection with an appropriate VA rating.

The E-BUS Distribution Module connects to the VCM-X Modular
Controller, VCM-X Expansion Module, or 12 Relay Expansion Module
using the I

2

C port. See Figure 4 below for wiring.

Any E-BUS module can be connected to each of the four E-BUS

Dis-

tribution Module’s output ports or can be daisy-chained together using
HSSC cables.

If using a spliced terminal connection for longer runs, one module can be
connected to the E-BUS Distribution Module and any additional modules
would be daisy-chained to the fi rst module. For more information, refer
to the E-BUS Distribution Module Technical Guide.

NOTE: Contact Factory for the correct HSSC cable length for

your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.

Advertising