Installation and wiring, Technical guide full digital module 5, Important wiring considerations – Orion System Full Digital Module User Manual

Page 5: Figure 3: full digital e-bus connection wiring

Advertising
background image

Technical Guide

Full Digital Module

5

Installation and Wiring

Important Wiring Considerations

Please carefully read and apply the following information when wiring
the Full Digital Module:

1. The 1 to 5 VDC signals for the Copeland Compressor

Speed need to use 18-gauge shielded twisted pair cable, and
the Drain wire must be the GND signal.

2. All 24 VAC wiring must be connected so that all ground

wires remain common. Failure to follow this procedure can
result in damage to the module and connected devices.

3. All wiring is to be in accordance with local and

national electrical codes and specifi cations.

4. Be sure that all wiring connections are properly inserted

and tightened into the terminal blocks. Do not allow wire
strands to stick out and touch adjoining terminals. This
could potentially cause a short circuit.

5. Be sure all modular wiring harness connectors are seated

fi rmly in their respective modular connectors on the circuit
board.

NOTE: The Compressor Relays on the Full Digital Module

are used rather than the relay outputs on the VCM-X
Modular series controller.

WARNING: Be sure all controllers and modules are

powered down before connecting or

disconnecting HSSC cables.

Figure 3: Full Digital E-BUS Connection Wiring

SHLD

SHLD

SHLD

OUT

OUT

OUT

COM

COM

COM

EXC

EXC

EXC

P4

P4

P4

BK

BK

BK

RD

RD

RD

WH

WH

WH

P2

P2

P2

P1

P1

P1

P3

P3

P3

P5

P5

P5

C1

C1

C1

C2

C2

C2

P6

P6

P6

SHLD

OUT

COM

EXC

P4

BK

RD

WH

P2

P1

P3

P5

AO1

SIG 1

SIG 2

SIG 3

SIG 4

AO2

GND

GND

GND

GND

C1

C2

P6

+5V

SIG 2

GND

OPTI

O

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

OE275-01 Suction

Pressure Transducer

OE370-23-FD-A

Full Digital Module

Copeland Digital

Compressor Controller B1

Copeland Digital

Compressor Controller A2

Copeland Digital

Compressor Controller A1

Copeland Digital

Compressor Controller B2

This Dip

Switch Is Not

Used For This

Application

This Dip

Switch Is Not

Used For This

Application

PWR

Connect To E-BUS

Distribution Module or

VCM-X Modular E-BUS Controller

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result in
damage to the boards.

HSSC Cable

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER

ALL RELAY OUTPUTS

ARE

COMPRESSOR A2 ENABLE

COMPRESSOR A1 ENABLE

R1

R4

R3

R2

COMPRESSOR B1 ENABLE
COMPRESSOR B2 ENABLE

ONLY.

1 AMP MAXIMUM LOAD.

HVAC UNIT CONNECTIONS