Installation and wiring, Technical guide full digital module 7, Modular cable connect to vcm-x modular controller – Orion System Full Digital Module User Manual

Page 7

Advertising
background image

Technical Guide

Full Digital Module

7

WARNING!!
Observe Polarity! All
boards must be wired with
GND-to-GND and 24 VAC-
to-24 VAC. Failure to
observe polarity could
result in damage to the
boards.

OE365-23-EBD E-BUS

Distribution Module

GND

-COMM

SHLD

+COMM

INPUT

+COMM

SHLD

-COMM

GND

+VDC

485 DRV

24VAC

GND

PWR

YS102308
REV 1
I2C TO COMM
DIST. BOARD

OUTPUT

Modular Cable

Connect To

VCM-X Modular Controller

HSSC Cable

Connect To E-BUS

Distribution Module

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

OE370-23-FD-A

Full Digital Module

+5V

SIG 2

GND

OPTI

O

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All boards must
be wired with GND-to-GND and 24
VAC-to-24 VAC. Failure to observe
polarity could result in damage to
the boards.

Installation and Wiring

WARNING: Be sure all controllers and modules are

powered down before connecting or

disconnecting HSSC cables.

Figure 4: VCM-X Modular Controller Connection to Full Digital Module