SMTS Technical Guide

VCM, VCM-X & VCB-X Controllers

37

VCB-X Controllers

SAT Reset Source

This confi guration option is not available if Single Zone VAV was
selected as the HVAC source. The Supply Air Setpoint can be “auto-
matically” adjusted based on a selected reset source. This screen allows
you to choose this source. Select No Reset for Single Zone VAV units.
Default is No Reset. The available selections are as follows:

 

No Reset

— No SAT Setpoint Reset will occur. The SAT

Setpoints

remain

fi xed.

 

Space Temperature

—The SAT Setpoints will be

adjusted based on the Space Temperature.

 

Outdoor Air

—The SAT Setpoints will be adjusted based

on the Outdoor Air Temperature.

 

Return Air

—The SAT Setpoints will be adjusted based on

the

Return

Air

Temperature.

 

Fan VFD Signal

—The SAT Setpoints will be adjusted

based on the VFD Signal. This is good for Adjusting the

Setpoints based on the building’s load by looking at the

VFD

speed.

NOTE:

This screen will be grayed-out if Single Zone VAV was selected

as the HVAC Mode Enable Source.

Fan Cycle Mode—

Touch the square button to select this item if

you want the HVAC unit’s Supply Fan to only run during

Heating or Cooling Mode. DO NOT select this item if you want

the HVAC unit’s Supply Fan to run continuously while in the

Occupied Mode, regardless of the Heating or Cooling Mode.

Has Head Pressure Control—

Touch the square button to

select this item if you have the EM1 Module installed and

confi gured and if a Head Pressure Sensor is installed for Head
Pressure

Control.

Has Water Side Condenser—

Touch the square button to

select this item if you have the EM1 Module installed and

confi gured and if using a Water Side Condenser.

Dehumidifi cation Control

Touch the radio button to select the type of Dehumidifi cation control.
Default is None.

None

—The unit does not have a Dehumidifi cation Mode.

Dehumidify in Occupied Vent Mode Only

—The unit

can only enter Dehumidifi cation during the Occupied Vent

Mode (when there is no call for Cooling or Heating).

Dehumidify in Vent Mode Anytime

—The unit can only

enter

Dehumidifi cation during the Vent Mode (when there

is no call for Cooling or Heating) in both the Occupied and

Unoccupied

operation.

Dehumidifi cation in All Modes Occupied

—This is

Occupied

Mode

Dehumidifi cation Priority. The unit can

enter

Dehumidifi cation during Cooling, Heating, or Vent

Modes, but only while in Occupied operation.

VCB-X Confi guration

Dehumidifi cation in All Modes Anytime

This is

Occupied and Unoccupied Dehumidifi cation Priority. The

unit can enter Dehumidifi cation during Cooling, Heating, or

Vent Modes while in Occupied or Unoccupied operation.

For units controlled by space humidity sensors, Dehumidifi cation is
initiated based on an Indoor Humidity Setpoint. For 100% OA units
(MUA), Occupied Dehumidifi cation is initiated based on an Outdoor Air
Dewpoint Setpoint. For MUA units, Unoccupied Dehumidifi cation can
only occur if the unit is confi gured for Night Setback recirculating opera-
tion and has a Space Humidity sensor and a Space Humidity Setpoint.

Reheat Type

This confi guration option is available if expansion module EM1 has been
installed and confi gured and if Dehumidifi cation has been confi gured.
If you need Reheat in the Dehumidifi cation mode, this screen allows
you to confi gure what kind of reheat will be used. The output(s) will be
staged or modulated to maintain the Active Supply Air Setpoint. Touch
the radio button to select the desired Reheat Type. Default is None.



None—

No Reheat.

 

On/Off HGR Relay—

Single On/Off Reheat stage (Reheat

Relay).

 

Modulating HGR

—Modulating Hot Gas Reheat

(MHGR)

 

Use Unit Heat for Reheat—

Using the unit’s heat as

Reheat when Hot Gas Reheat is not available.

 

Mod HGR AND Unit Heat

—Using MHGR as the 1

st

form of Reheat, supplemented by unit Heat if necessary.

 

On/Off HGR AND Unit Heat

—Using “Reheat Relay”

stage as the 1

st

form of Reheat, supplemented by unit Heat

if

necessary.

NOTE:

This screen will be grayed-out if not using Dehumidifi cation.

Reversing Valve ( Heat Pump Confi guration)

If you are using a Heat Pump, touch the radio button to select the desired
Reversing Valve Signal if your Heat Pump unit activates its reversing
valve during Cooling or Heating operation. Default is None.



None—

Not a Heat Pump and no externally controlled

reversing

valve.

 

Air to Air Heat Pump Fail to Heating—

Air to Air Heat

Pump and Reversing Valve fails to Heating.

 

Air to Air Heat Pump Fail to Cooling—

Air to Air Heat

Pump and Reversing Valve fails to Cooling.

 

Water Source Heat Pump Fail to Heating—

Water

Source Heat Pump and Reversing Valve fails to Heating.

 

Water Source Heat Pump Fail to Cooling—

Water

Source Heat Pump and Reversing Valve fails to Cooling.